The pressure gauge was removed for testing, also the blow down skin fitting needed replacement because of a leak in the valve casting.
This 3/4" gate valve on investigation was found to have a long split in the body, probably cause by old frost damage.
Some time ago we had acquired a useful dead weight pressure gauge test set, so used this to check the accuracy of Consuta's gauge.

The photo shows the gauge reading using 180 lbs weight (9 of 20 lb each), plus 2lbs added due to the weight of the deadweight mounting pad, so the gauge should really be reading 182 psi.
The weight pad on the right is being used, the gauge pointer is masking the red line. So 2lbs low but still pretty good accuracy.